ABB FI/LS switch
Only 2 pieces in stock at supplier
Product details
ABB Stotz S&J RCD/MCB DS201A-B16/0.3
Manufacturer: ABB Stotz S&J
Designation: RCD/MCB 6kA, 1p+N
Type: DS201A-B16/0.3
Number of poles (total): 2
Number of protected poles: 1
Rated voltage: 230 V
Rated current: 16 A
Rated residual current: 0.3 A
Residual current type: A
Rated tripping capacity according to EN 61009: 6 kA
Rated tripping capacity according to IEC 60947-2: 10 kA
Impulse current resistance: 0 kA
Type of voltage: AC
Frequency: 50/60 Hz
Tripping characteristic: B
Switched neutral conductor: yes
With locking device: no
Overvoltage category: 3
Degree of pollution: 2
Ambient temperature during operation: -25 to 55 °C
Width in division units: 2
Installation depth: 69 mm
Flush-mounted: no
False tripping protection: no
Protection class (IP): IP2X
RCD/MCBs (RCBOs) provide personal and property protection as well as protection against electrically ignited fires in accordance with DIN VDE 0100-410 and DIN VDE 0100-530. They ensure protection of single-phase circuits against overload and short-circuit currents, protection against sinusoidal alternating currents and pulsating currents with a smooth DC fault current component of up to 6 mA to ground. They also provide fault protection (protection against indirect contact), additional protection (with I?n = 30 mA), and fire protection (with I?n = 300 mA). They comply with product standards IEC/EN 61009-1 (VDE 0664-20), IEC/EN 61009-2-1 (VDE 0664-21).
Areas of application include household, commercial, and industrial uses. The extensive range of accessories provides everything you need for your installation tasks. Numerous approvals make the DS201 suitable for worldwide use.
Rated breaking capacity according to IEC/EN 61009 Icn = 6 kA.
RCBO DS201 A Type A is 1-pole protected (MCB), 2-pole switching.
EAN: 8012542643517.
Circuit breaker type | Miniature circuit-breaker/residual current circuit-breaker combination |
Length | 69 mm |
Width | 2 mm |
mounting style | Top-hat rail |
number of poles | 1 |
Item number | 20027640 |
Manufacturer | ABB |
Category | Residual-current device |
Manufacturer no. | 2CSR255180R3165 |
Release date | 16/3/2022 |
Circuit breaker type | Miniature circuit-breaker/residual current circuit-breaker combination |
mounting style | Top-hat rail |
number of poles | 1 |
Tripping characteristic | B |
Rated current | 16 A |
Rated current | 0.3 A |
Rated voltage | 240 V |
voltage type | AC |
Rated insulation voltage Ui | 500 V |
Residual current (rated differential current) | 0.30 A |
Protection type (IP code) | IP20 |
Country of origin | China |
Manufacturer commitment | SBTi |
CO₂-Emission | |
Climate contribution |
Items per sales unit | 1 Piece |
Length | 69 mm |
Width | 2 mm |
Product Safety |
30-day right of return if unopened
Compare products
Goes with
Reviews & Ratings
Statutory warranty score
How often does a product of this brand in the «Residual-current device» category have a defect within the first 24 months?
Source: Galaxus- 1.Siemens0 %
- 4.Eaton0,1 %
- 5.Hager0,2 %
- 6.ABB0,3 %
- 7.Steffen0,6 %
Statutory warranty case duration
How many working days on average does it take to process a warranty claim from when it arrives at the service centre until it’s back with the customer?
Source: Galaxus- ABBNot enough data
- BrennenstuhlNot enough data
- EatonNot enough data
- HagerNot enough data
- Schneider ElectricNot enough data
Unfortunately, we don't have enough data for this category yet.
Return rate
How often is a product of this brand in the «Residual-current device» category returned?
Source: Galaxus- 2.Brennenstuhl1,6 %
- 2.Schneider Electric1,6 %
- 4.ABB1,7 %
- 5.Siemens2 %
- 6.Eaton3,8 %